Features:
Rated voltage: 0.6/1kV AC
Operating voltage: 1.5 kV DC (in accordance with EN 50618)
Insulation resistance: 1000 MΩ/km
Maximum cable temperature during operation: +90°C
Maximum cable temperature during long-term operation: +120°C/20000h
Minimum ambient temperature for permanently installed cables: -40°C
Minimum cable laying temperature: -25°C
50Hz Test voltage: 4000V
Resistance to UV radiation, ozone, and weather conditions: In accordance with EN 50618
Flame retardant: In accordance with DIN EN 60332-1
No aggressive fumes during combustion
Minimum bending radius for fixed connections: 4 x Ø
Expected service life: 25 years
Specifications:
Standard: PN-EN 50618:2015-03
Minimum cable length: 1m
Material:
Conductors: Tinned, flexible copper conductors, Class 5 according to PN-EN 60228
Insulation: Cross-linked halogen-free polymer
Sheath: Halogen-free, cross-linked polymer
Insulation color: White
Application:
Used in photovoltaic systems for connections between individual photovoltaic modules and between modules and inverters.
Packaging:
Coils and spools.